VM5-320HUL , 320HUM

Technical parameters
Rated current (A) | 63A, 80A, 100A, 125A, 140A, 160A, 180A, 200A, 225A, 250A, 320A |
Rated operating voltage (AC50~60Hz (V)) | AC800&1000 |
Rated insulation voltage (V) | 1000V |
Rated impulse withstand voltage Uimp (kV) | 8kV |
Pole number | 3P |
Breaking capacity | L , M |
Rated ultimate short circuit breaking capacity(kA) (lcu; AC 50/60 Hz; AC800V) | 30 , 50 kA |
Rated ultimate short circuit breaking capacity(kA) (lcu; AC 50/60 Hz; AC1000V) | 15 , 30 kA |
Rated service short circuit breaking capacity(kA) (lcs; AC 50/60 Hz; AC800V) | 30 , 50 kA |
Rated service short circuit breaking capacity(kA) (lcs; AC 50/60 Hz; AC1000V) | 12 , 18 kA |
Mechanical durability (times) | 12000(times) |
Electrical durability (AC800V times) | 1000(times) |
Electrical durability (AC1000V times) | 1000(times) |
With (mm)* Heigh (mm)* Depth (mm) | 185(mm) × 112.5(mm) × 106.5(mm) |
Isolatiion function | Have isolation function |
Optional trip unit (TA) | Thermally adjustable(0.7~1.0) Magnetic adjustable(5~10) |
Optional trip unit (TAL) | Thermally adjustable(0.7~1.0) Magnetic fixation(10In) |