VOZWEI-Surge protection device
برقگیر تابلویی سری VPH-880 با طراحی ترکیبی B+C و کنتاکت سیگنال، گزینه ای مناسب جهت استفاده در نیروگاه های خورشیدی با ولتاژ کاری 800 ولت است.

Technical parameters
Parameter\Model | VPH880-12.5/3P+1P(T1+T2) |
SPD according to EN/IEC 61643-11 | T1+T2 |
Network | IT-TN |
Application | L-PE |
Maximum continuous operating voltage Uc | 880V@ 50Hz/ 60Hz |
Impulse current, Iimp (10/350μs) | 12.5kA |
Nominal discharge current In (8/20μs) | 20kA |
Maximum discharge current Imax (8/20μs) | 50kA |
Protection Voltage, Up | ≤3.4kV |
Internal protective devices | Built- in thermal tripping device |
Maximum overcurrent protection (fuse rating) | 250A gL/gG |
Shortcircuit proof at maximum overcurrent protection 25kArms | 25kArms |
Response time | ≤25ns |
Cross- sectional area of input/ output wire | 6mm2 ~ 35mm2 |
Bare wire connection length | 12.5mm |
Installation wiring torque | 3Nm |
Failure indicator | The indication window turns into red when damaged |
Remote signaling | Normally closed remote signal contact (RSC),NC-COM-NO contact |
Performances of remote signal contact | AC: 250V/0.5A; DC: 250V/0.1A, 125V/0.2A, 75V/0.5A |
Cross- sectional area of the signaling wire | Maximum 1.5 mm2 |
Installation mode | Using 35mm standard DIN rail |
Housing material | PBT UL94-V0 |
Enclosure protection degree | IP20 |
Operation temperature | -40°C ~ +80°C |
Relative humidity | ≤95% (25°C) |
Altitude | ≤3000m |
Electric clearance required by EN 60664-1:2003 | ≥6mm |
Dimensions (without terminals) | 90.0mm×72.0mm×77mm |
Module pluggable | Pluggable module |